PONOPT FIELD NOTES · Predictive maintenance

Predictive Maintenance for Pumps, HVAC and Elevators: Data to Start With

Which data actually matter for predictive maintenance of pumps, HVAC and elevators: vibration, temperature, pressure, current and fault logs, with a practical start matrix.

Start with the failure mode most likely to stop each asset, then capture the cheapest signal that reveals it. For pumps, log bearing-housing vibration, temperature and differential pressure. For HVAC, mine the building management system for air and water temperatures, pressure drops and fan current. For elevators, read controller fault logs, door-cycle counts and starts. Trend the drift from a baseline and act on it, not on a single reading.

Key takeaways

  • Predictive maintenance is condition-based: you act on measured degradation rather than calendar time, so choosing the right data separates useful signals from noise.
  • For pumps the first signals that pay off are bearing-housing vibration, temperature and differential pressure or flow.
  • For HVAC, mine the data a building management system already records — filter pressure drop, fan current, temperatures and valve positions — before buying sensors.
  • For elevators, start with controller fault logs, door-cycle counts and starts before adding third-party hardware to safety-regulated equipment.
  • A single reading means little; you need a baseline captured at defined operating points and enough history to separate drift from noise.
  • Cross-check alarm thresholds with standards such as ISO 10816-3/-7 and with manufacturer guidance.

Start from the failure mode, not the catalogue

Predictive maintenance (also called condition-based maintenance) relies on measurements that detect the onset of degradation so you can intervene before a component is significantly damaged. The U.S. DOE's FEMP best-practice material, hosted by Pacific Northwest National Laboratory, contrasts this with preventive maintenance driven by time or run-hours and with reactive maintenance that repairs after failure. Because a predictive program schedules work from the machine's actual condition, it can cut unplanned downtime; the same guidance cites planning-level estimates of roughly 8-12% savings over a preventive-only program, with larger gains where reactive maintenance dominates. Treat these as planning figures, not guarantees.

The common mistake is to instrument everything. A more effective approach is to pick the asset most likely to fail, identify its dominant failure mode, then choose the cheapest signal that reveals it plus a few context readings. The condition-monitoring framework in ISO 13374-1 describes the pipeline you are really building: collecting, processing and presenting data so you can assess current health, predict failure and generate recommended actions. Keep that pipeline simple at the start — it is easier to add useful data later than to clean up noise.

Pumps: vibration, temperature and differential pressure

For a rotodynamic (centrifugal) pump, the measurements that pay off first are overall vibration velocity taken on the bearing housing, bearing and motor temperature, and a hydraulic signal such as differential pressure or flow. ISO 10816-7 gives guidance for evaluating vibration on rotodynamic pumps above 1 kW measured on the bearing housing, and uses two complementary criteria: the absolute magnitude of vibration and its change over time. ISO 10816-3 supplies advised severity zones — for example new machinery, unrestricted long-term operation, restricted operation and the damage range — that facilities commonly use as starting thresholds for medium machines.

Link the signal to the failure. Rising broadband vibration often points to imbalance, misalignment or looseness; creeping temperature suggests failing bearings or motor overload; a falling head or differential pressure at constant speed and flow hints at impeller wear, internal recirculation or erosion; cavitation shows up as noise and unstable pressure and flow. Whatever you measure, log the operating point — speed, load and whether a variable-speed drive is active — because vibration and temperature only make sense at a known condition.

  • Rising vibration: imbalance, misalignment, looseness
  • Creeping temperature: bearing wear, motor overload
  • Falling head at constant speed: impeller wear, erosion, recirculation
  • Noise plus unstable pressure/flow: cavitation

HVAC: mine the building management system first

The cheapest predictive maintenance for HVAC is often data you already own. Air-handling units, fan-coils and chillers are usually controlled by a BMS that records supply, return and mixed-air temperatures, duct static pressure, valve and damper positions, and fan or pump current. Filter fouling shows as a rising differential pressure across the filter; cooling-coil fouling as a smaller temperature difference across the coil or a drifting valve position; fan degradation as rising current for the same airflow. Baseline these at stable conditions and watch the drift.

Chillers add a refrigerant-side view: evaporator and condenser approach temperatures, superheat and subcooling, and refrigerant pressures drift as the charge changes or tubes foul. Published control and fault-detection logic — for example the rules for air-handling units in ASHRAE Guideline 36 — gives a practical template for which comparisons to compute. Note that these are performance and control data, not a replacement for periodic physical checks such as belt tension or refrigerant leak detection; combine both sources.

Elevators: controller fault logs and cycle counts before extra hardware

Much of the data for elevator predictive maintenance is already digital. Modern controllers keep fault logs with timestamps and often count door operations, starts and running hours, and record motor-drive temperature and current. In many fleets, doors produce a large share of service calls, so door-cycle counts and door-related fault codes are a sensible first signal. Ride-quality vibration captured on scheduled walkthroughs is useful and does not require an always-on sensor.

Adding sensors or IoT devices to a lift is not like doing so on a pump, because lifts are safety-regulated and connected to the safety chain. Third-party monitoring must not compromise safety functions; in practice you need the manufacturer or authorized maintainer involved, plus compliance with the applicable local code and standards such as the ISO 8100 series — its part 2, published in 2026, covers verification of door locks, safety gears, overspeed governors and buffers. Start by extracting the data the controller already records before attaching anything.

Turning signals into decisions: baselines, trends and pilots

A single reading means little on its own. You need a baseline captured at defined operating conditions and enough history to separate a real drift from noise or seasonal load change. Give the pilot three to six months to build that history before trusting alarms. Use both absolute thresholds — drawn from standards or OEM advice — and relative change from baseline; ISO 10816-7, for example, evaluates vibration by magnitude and by change over time.

Scope the pilot to the most critical or most failure-prone asset in each category: one pump, one air-handling unit or chiller, one high-traffic elevator. Define in advance what a technician will do when an alarm fires, because a predictive program fails when alerts have no owner or assigned response. Document each decision so the next season's thresholds become more accurate.

Minimum-viable-data start matrix for pumps, HVAC and elevators

Pick one primary degradation signal per asset plus two or three context readings. Capture the context at the same time as the primary signal so trends stay comparable, then log for 30-90 days before setting alarm bands.

  1. Rotodynamic pump — primary: overall vibration velocity (mm/s RMS) on drive-end and non-drive-end bearing housings; context: speed/RPM, flow, discharge pressure.
  2. Pump motor — primary: winding or housing temperature and motor current or absorbed power; context: ambient temperature.
  3. Pump hydraulics — primary: differential pressure or head plus flow; raise an alert on drift at constant speed.
  4. Air-handling unit / fan — primary: differential pressure across the filter (fouling) and fan motor current; context: supply, return and mixed-air temperatures.
  5. Cooling coil — primary: temperature difference across the coil and valve position at stable load; fouling raises required valve opening or cuts the delta-T.
  6. Chiller — primary: evaporator and condenser approach temperatures plus superheat and subcooling; context: chilled-water supply temperature and load.
  7. Elevator — primary: controller fault-log entries with timestamps, plus door-cycle counts and starts per hour; context: traffic pattern and time of day.
  8. Elevator drive — primary: drive current and temperature; capture cabin ride-quality vibration on periodic inspections rather than as a continuous stream.

Questions people ask

What is the single most useful signal for predictive maintenance of a pump?

The most useful first signal is overall vibration velocity measured on the pump bearing housing, ideally paired with bearing or motor temperature. For rotodynamic pumps above 1 kW, ISO 10816-7 provides guidance based on bearing-housing measurements and uses two criteria: the absolute vibration magnitude and its change over time. Add a hydraulic reading — differential pressure or flow at constant speed — because it reveals impeller wear, erosion or internal recirculation that vibration alone may miss. Vibration and temperature only become meaningful when you log the operating point, such as speed, load and variable-speed-drive status, at the same time.

How much baseline data do I need before setting alarm thresholds?

There is no fixed number, but a practical rule is to collect 30-90 days of data across stable operating modes, ideally covering different loads and seasonal conditions, so you can separate a genuine drift from noise. Set thresholds in two ways: an absolute value taken from a standard such as ISO 10816-3 or ISO 10816-7, or from the manufacturer, plus a relative change from the baseline. For variable-speed equipment, build history by operating mode rather than by calendar date, otherwise load changes will mask degradation.

Can predictive maintenance for HVAC run on existing BMS data instead of new sensors?

Yes, and for ventilation and air conditioning it is usually the most sensible first step. A building management system typically already records supply, return and mixed-air temperatures, duct static pressure, valve and damper positions, and fan and pump current. From these you can compute useful indicators such as pressure drop across the filter, temperature difference across the coil, and rising current for the same airflow. This is inexpensive and gives trends quickly, but it does not replace physical checks of belts, refrigerant leaks or electrical contacts. Add dedicated sensors only where the BMS signal is insufficient.

What does ISO 10816 say, and does it cover HVAC pumps?

The ISO 10816 series defines vibration zones and limits for evaluating machine condition from measurements on non-rotating parts. ISO 10816-3 gives advised severity zones for medium electric machines — for example levels for new machinery, unrestricted long-term operation, restricted operation and the damage range. ISO 10816-7 addresses rotodynamic pumps above 1 kW and evaluates vibration by absolute level and by change over time. Both apply to pumps used in heating, ventilation and air conditioning, though exact limits depend on the machine group, mounting type and the manufacturer's guidance, so treat published figures as starting points.

Can I add vibration sensors to an elevator for predictive maintenance?

Technically yes, but an elevator is a safety-regulated machine connected to the safety chain, so any third-party device must not compromise safety functions. In practice this requires coordination with the manufacturer or an authorized maintenance contractor and compliance with applicable codes and standards, such as the ISO 8100 series; part 2 covers verification of door locks, safety gears, overspeed governors and buffers. Before adding sensors, extract what the controller already records: fault logs, door-cycle counts, starts, and drive current and temperature. Cabin vibration can be collected on periodic inspections rather than streamed continuously.

How often should I sample or refresh condition data?

It depends on how fast the failure develops and how the equipment is operated. For slow degradations such as bearing wear or filter fouling, regular readings from weekly to monthly are enough as long as the operating mode is recorded. For fast processes such as cavitation or sudden load swings, more frequent or continuous measurement helps. Data from BMS and controllers usually arrives at a short interval already, so the priority is averaging over stable operating modes and computing a trend, not maximizing sampling frequency for its own sake. Consistency of measurement conditions matters more than the highest possible rate.

Sources and further reading

Sources were checked when this page was generated. Confirm changing dates, rules and prices with the original publisher.

  1. ISO 13374-1:2003 - Condition monitoring and diagnostics of machines - Data processing, communication and presentation - Part 1: General guidelinesInternational Organization for Standardization
  2. O&M Best Practice Issue Discussion: Maintenance ApproachesPacific Northwest National Laboratory (DOE FEMP)
  3. Understanding the ISO 10816-3 Vibration Severity ChartAcoem USA
  4. NEN-ISO 10816-7:2009 - Mechanical vibration - Evaluation of machine vibration ... Part 7: Rotodynamic pumpsNEN (Netherlands Standardization Institute)
  5. ISO 8100-2:2026 - Лифты для транспортировки людей и грузов. Часть 2International Organization for Standardization